DZ47-631p
DZ47-631

DZ47-63 Miniature Circuit Breakers

1. Application

DZ47-63 Miniature Circuit Breakers are mainly used in AC 50Hz circuit with rated voltage 230V/400V, rated current up to 63A or less, and rated operating breaking capacity no more than 4500A power distribution system, protection of control circuit against short circuit and overload current fault. And also have circuit control and isolation function.

2. Technical data

Model

Versions

Rated voltage(v) :

230V/400V(1P)、400V(2P、3P、4P)

Rated current(A) :

6、10、16、20、25、32、40、50、63

Poles :

1P、2P、3P、4P

Rated breaking capacity(A):

4500

Tripping characteristic:

Mark 2

Mechanical life & Electrical life:

4000

Nominal cross section area 
S (mm2):

Mark 3

Tightening torque (N-m):

2.5

Pollution Degree:

2

Protection class:

IP20

Overvoltage category :

Class II

Mark 2:Tripping characteristic (temperature 30℃):

Model

Rated current(A)

Initial situation

Test current

Tripping time

Test result

Remarks

Delay

≤63

Cold

1.13In

≤1h

Not-tripping

 

Delay

≤63

Following No.1 test

1.45In

<1h

Tripping

Current stablely raised to specified value in 5s

Delay

≤32

Cold

2.55In

1<t<60s

Tripping

 

Delay

>32

Cold

2.55In

1<t<120s

Tripping

 

Instant

Any value

Cold

3、5、10In

≤0.1s

Not-tripping

B、C、D

Instant

Any value

Cold

5、10、20In

<0.1s

Tripping

B、C、D

Mark 3: Normal cross section area: <50mm² , Tightening torque: 2.5N.m

In(A)

Nominal cross section area S (mm²)

In≤6

1

6<In≤13

1.5

13<In≤20

2.5

20<In≤25

4

25<In≤32

6

32<In≤50

10

50<In≤63

16

3. Working and the installing condition

3.1 Ambient max temperature is no more than +40℃, minimum temperature is not less than -5℃. No more than +35℃ within 24 hours;

3.2 altitude is no more than 2000m;

3.3 when the highest temperature reaches 40℃ the air relative humidity of the installing place can't exceed 50%, when in the low temperature it will have the relative higher humidity. When the average largest relative humidity in the most humiddest it is month no more than 90%, then the monthly-average temperature is no more than 25℃. We must take measure of the dew in the surface of the product due to the 
temperature;

3.4 installing method: Din rail embedded

4. Overall and Mounting dimensions (mm)

DZ47-632